DiagCode
State Name
8002
Safe
8003
Lock
8010
Output Disable Process control is not active.
8000
Output Enable Process control is active and safety is enabled.
4.6.6.18
SF_EDM
Standards
Requirements
IEC 60204-1, Ed.
Section 9.2.2: Stop function categories; Category 0
5.0: 2003
EN 954-1: 1996
5.2: Stop function; stop initiated by protective devices shall put the machine in a safe
state
6.2: Specification of categories: Fault detection (of the actuator, e.g. open circuits)
ISO 12100-2:
4.11.4: Restart following power failure/spontaneous restart
2003
EN 954-1: 1996
5.4 Manual reset
30.03.2017
State Description and Output Setting
Triggered safety function.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
Safety function startup inhibit is active. Reset required.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
Ready = TRUE
S_OutControl = FALSE
Error = FALSE
Ready = TRUE
S_OutControl = TRUE
Error = FALSE