AC500-S Safety Modules
DI581-S digital safety input module > Technical data
Signal voltage
Data
Input signal voltage
Signal 0
Undefined signal
Signal 1
Input current per channel
Data
Input voltage +24 V, typically
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Cable length
Data
Max. cable length, shielded
Max. cable length, unshielded
3.3.9.2
Technical data of non-safety test pulse outputs
DANGER!
Exceeding the maximum process or supply voltage range (< –35 V DC or > +35 V DC) could lead to
unrecoverable damage of the system.
104
AC500-S
Value Unit
24 V DC
–3 ... +5 V
> +5 ... < +15 V
+15 ... +30 V
Value Unit
7 mA
< 1 mA
> 4 mA
< 8 mA
Value Unit
1000 m
600 m