ABB AC500-S Safety User Manual page 343

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
State Name
8003
Wait for Reset
8005
Safe
8011
Muting For-
ward Start
8012
Muting For-
ward Active
8112
Muting Back-
ward Active
8122
Muting Back-
ward Start
30.03.2017
State Description and Output Setting
Safety demand or errors have been detected and are now cleared. Oper-
ator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Safety function activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
Muting forward, sequence is in starting phase and no safety demand.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Muting forward, sequence is active.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting backward, sequence is active.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
Muting backward, sequence is in starting phase and no safety demand.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
343