Table 44: FB-specific status codes (no error):
DiagCode
State Name
0000
Idle
8005
ModeChanged State after activation or when S_ModeX has changed (unless locked) or
8000
ModeSelected Valid mode selection, but not yet locked.
8004
ModeLocked
4.6.6.5
SF_EmergencyStop
Standards
Requirements
EN 418: 1992
3. Definitions
4.1.12 ... Resetting the control device shall not by itself cause a restart command.
EN 954-1: 1996
5.4 Manual reset
ISO 12100-2:
4.11.4 Restart following power failure/spontaneous restart
2003
EN 16204-1, 1997 9.2.2. Stop Functions
30.03.2017
State Description and Output Setting
The function block is not active (initial state).
Ready = FALSE
Error = FALSE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
after Reset of an error state.
Ready = TRUE
Error = FALSE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
Ready = TRUE
Error = FALSE
S_AnyModeSel = TRUE
S_ModeXSel = Selected X is TRUE, others are FALSE.
Valid mode selection is locked.
Ready = TRUE
Error = FALSE
S_AnyModeSel = TRUE
S_ModeXSel = Selected X is TRUE, others are FALSE.
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib