Range
0 ... 20 mA
Overflow
:
> 23.519
23.519
Overrange
:
20.000723
20
Nominal
range
:
0
Underrange
–0.000723
:
–1.481
Underflow
< –1.481
* In these cases, the analog channels are passivated and "0" process values are delivered to the Safety
CPU.
3.5.3 Mounting, dimensions and electrical connection
The input modules can be plugged only on spring-type TU582-S I/O Terminal Unit. The unique mechanical
coding on I/O Terminal Units prevents a potential mistake of placing the Non-safety I/O module on Safety I/O
Terminal Unit and the other way around.
Installation and maintenance have to be performed according to the technical rules, codes and relevant
standards, e.g. EN 60204 part 1, by skilled electricians only.
30.03.2017
AI581-S analog safety input module > Mounting, dimensions and electrical connection
4 ... 20 mA
Digital value (dec)
32767*
:
:
> 22.81
32512*
22.81
32511
:
:
20.000578
27649
20
27648
:
:
16
20736
:
:
4
0
0 ... 20 mA
3.999421
–1
:
:
1.185
–2048
0 ... 20 mA
< 1.185
–2049*
:
–32768*
AC500-S
AC500-S Safety Modules
Digital value (hex)
7FFF*
:
7F00*
7EFF
:
6C01
6C00
:
5100
:
0000
4 ... 20 mA
0 ... 20 mA
–1
FFFF
:
:
–4864
F800
4 ... 20 mA
0 ... 20 mA
–4865*
F7FF*
:
:
–32678*
8000*
4 ... 20 mA
FFFF
:
ED00
4 ... 20 mA
ECFF*
:
8000*
139