Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Example for SF_MutingPar in forward direction with four sensors
1
If the muting sensors MutingSwitch11 (MS_11) and MutingSwitch12 (MS_12) are activated by the product
within the time DiscTime11_12, muting mode is activated (S_MutingActive = TRUE).
2
Muting mode remains active as long as MutingSwitch11 (MS_11) and MutingSwitch12 (MS_12) are activated
by the product. The product may pass through the light curtain without causing a machine stop.
3
Before muting sensors MutingSwitch11 (MS_11) and MutingSwitch12 (MS_12) are disabled, muting sensors
MutingSwitch21 (MS_21) and MutingSwitch22 (MS_22) must be activated. This ensures that muting mode
remains active. The time discrepancy between switching of MutingSwitch21 and MutingSwitch22 is moni-
tored by the time DiscTime21_22.
4
Muting mode is terminated if either muting sensor MutingSwitch21 (MS_21) or MutingSwitch22 (MS_22) is
disabled by the product. The maximum time for muting mode to be active is the MaxMutingTime.
Muting Conditions
Forward Direction
348
Transmitter
MS_11
MS_21
MS_12
MS_22
Receiver
Transmitter
MS_11
MS_21
MS_12
MS_22
Receiver
Transmitter
MS_11
MS_21
MS_12
MS_22
Receiver
Transmitter
MS_11
MS_21
MS_12
MS_22
Receiver
AC500-S
Danger
zone
Danger
zone
Danger
zone
Danger
zone