Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Fig. 108: Timing diagram for SF_ESPE: S_StartReset = FALSE, S_AutoReset = TRUE, Start, normal opera-
tion, safety demand, restart
The function block detects a static TRUE signal at Reset input.
Error Behavior
S_ESPE_Out is set to FALSE. In case of a static TRUE signal at the Reset input, the DiagCode output indi-
cates the relevant error code and the Error output is set to TRUE.
To leave the error states, the Reset must be set to FALSE.