ABB AC500-S Safety User Manual page 299

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
State Name
8005
Wait for Reset
2
8000
Safety Output
Enabled
4.6.6.7
SF_GuardMonitoring
Standards
Requirements
EN 953: 1997
3.3.3 Control Guard
n
n
EN 1088: 1995
3.2 Interlocking Guard
n
n
n
EN 954-1: 1996
5.4 Manual reset
ISO 12100-2:
4.11.4 Restart following power failure/spontaneous restart
2003
30.03.2017
State Description and Output Setting
Activation is TRUE. S_ESPE_In = TRUE. Check for S_AutoReset or wait
for rising trigger of Reset.
Ready = TRUE
S_ESPE_Out = FALSE
Error = FALSE
Activation is TRUE. S_ESPE_In = TRUE. Functional mode with
S_ESPE_Out = TRUE.
Ready = TRUE
S_ESPE_Out = TRUE
Error = FALSE
The hazardous machine functions "covered" by the guard cannot operate until the
guard is closed;
Closing the guard initiates operation of the hazardous machine function(s).
The hazardous machine functions "covered" by the guard cannot operate until the
guard is closed;
If the guard is opened while the hazardous machine functions are operating, a stop
instruction is given;
When the guard is closed, the hazardous machine functions "covered" by the
guard can operate, but the closure of the guard does not by itself initiate their oper-
ation.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
AC500-S
299