ABB AC500-S Safety User Manual page 391

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Function Block-Specific Error and Status Codes
Table 85: FB-specific error codes
DiagCode
State Name
C001
Reset Error 1
C011
Reset Error 21 Static Reset signal or same signals at EDM1 and Reset (rising trigger at
C021
Reset Error 22 Static Reset signal or same signals at EDM2 and Reset (rising trigger at
C031
Reset Error 23 Static Reset signal or same signals at EDM1, EDM2, and Reset (rising
C041
Reset Error 31 Static Reset signal or same signals at EDM1 and Reset (rising trigger at
C051
Reset Error 32 Static Reset signal or same signals at EDM2 and Reset (rising trigger at
C061
Reset Error 33 Static Reset signal or same signals at EDM1, EDM2, and Reset (rising
30.03.2017
State Description and Output Setting
Static Reset signal in state 8001.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset and EDM1 at the same time) in state C010.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset and EDM2 at the same time) in state C020.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
trigger at Reset, EDM1, and EDM2 at the same time) in state C030.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset and EDM1 at the same time) in state C040.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Reset and EDM2 at the same time) in state C050.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
trigger at Reset, EDM1, and EDM2 at the same time) in state C060.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
391