AC500-S Safety Modules
Generic Safety I/O module behaviour > Safety I/O module states
ID*
From
(14)
RUN (channel
passivation &
reintegration)
(15)
INIT
(16)
RUN (user
acknowledge-
ment request)
(17)
RUN (user
acknowledge-
ment request)
(18)
RUN (module
passivation with
a command)
(19)
RUN (module
passivation)
(20)
RUN (user
acknowledge-
ment request)
(21)
RUN (module
passivation)
(22)
RUN (user
acknowledge-
ment request)
(23)
RUN (user
acknowledge-
ment request)
(24)
RUN (module
passivation with
a command)
68
To
Description
INIT
Powering off/on
INIT
Powering off/on
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
INIT
Powering off/on
RUN (module
PROFIsafe watchdog, PROFIsafe communication
passivation)
error or undervoltage/overvoltage was identified.
Note: In this transition, it is possible that
WD_timeout bit of PROFIsafe F-Host instance
toggles if watchdog timeout is periodically recog-
nized by the Safety I/O module.
RUN (module
If the threshold shut-down value was not reached
passivation with
during process undervoltage or overvoltage
a command)
phase and the process voltage is back in the
normal range, the Safety I/O module reintegrates
and would go to RUN (ok) state automatically, but
short time before the "activate_FV_C = 1" com-
mand was sent from the PROFIsafe F-Host
stack, which leads the Safety I/O module to RUN
(module passivation with a command) state.
RUN (module
Process undervoltage/overvoltage was identified.
passivation)
RUN (user
n
acknowledge-
ment request)
n
n
RUN (ok)
n
n
RUN (module
"activate_FV_C = 1" command was sent from the
passivation with
PROFIsafe F-Host
a command)
SAFE STOP
Fatal error(s) (CPU test, RAM test, etc. failed)
took place
AC500-S
Module error (watchdog or communication
error (CRC)) is gone.
and
Command activate_FV_C = 0
then
Safety I/O module sets OA_Req_S = 1
OA_Req_S = 1 was set by the Safety I/O
module after the module error is gone.
OA_C (positive edge) was set by the PROFI-
safe F-Host for the given Safety I/O module
30.03.2017