ABB AC500-S Safety User Manual page 291

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Fig. 105: Timing diagram for SF_EmergencyStop: S_StartReset = FALSE, S_AutoReset = TRUE, Start,
normal operation, safety demand, restart
The function block detects a static TRUE signal at Reset input.
Error Behavior
S_EStopOut is set to FALSE. In case of a static TRUE signal at the Reset input, the DiagCode output indi-
cates the relevant error code and the Error output is set to TRUE.
To leave the error states, the Reset must be set to FALSE.
30.03.2017
AC500-S
291

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents