DiagCode
State Name
C050
EDM Error 22
C060
EDM Error 23
C070
EDM Error 31
C080
EDM Error 32
C090
EDM Error 33
C111
Init Error
30.03.2017
State Description and Output Setting
The signal at EDM2 is not valid in the initial actuator state. In state 8010
the EDM2 signal is FALSE and the monitoring time has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
The signals at EDM1 and EDM2 are not valid in the initial actuator states.
In state 8010 the EDM1 and EDM2 signals are FALSE and the monitoring
time has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
The signal at EDM1 is not valid in the actuator switching state.
In state 8000 the EDM1 signal is TRUE and the monitoring time has
elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
The signal at EDM2 is not valid in the actuator switching state.
In state 8000 the EDM2 signal is TRUE and the monitoring time has
elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
The signals at EDM1 and EDM2 are not valid in the actuator switching
state. In state 8000 the EDM1 and EDM2 signals are TRUE and the moni-
toring time has elapsed.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
Similar signals at S_OutControl and Reset (R_TRIG at same cycle)
detected (may be a programming error)
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE