Parameterization; Circuit Examples - ABB AC500-S Safety User Manual

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

3.3.6 Parameterization

The arrangement of the parameter data is performed by your system configuration software PS501 Control
Builder Plus V2.2.1 (or newer) / ABB Automation Builder 1.0 (or newer). ABB GSDML file for PROFINET
devices can be used to configure DI581-S parameters in 3
The parameter setting directly influences the functionality of modules and reachable SIL (IEC 61508 ed. 2
and IEC 62061) and PL (ISO 13849).
No.
Name
1
Check supply
2
Configuration
3
Test pulse
4
Input delay
5
Discrepancy time*
* Available only for "2 channel equivalent" and "2 channel antivalent" configuration

3.3.7 Circuit examples

Examples of electrical connections and reachable SIL (IEC 61508 ed. 2 and IEC 62061), Category (EN 954)
and PL (ISO 13849) with DI581-S module are presented below.
NOTICE!
Whenever DC = High is used in the circuit examples for safety digital inputs, the following measure
from ISO 13849-1 [10] is used in DI581-S module: Cross monitoring of input signals and intermediate
results within the logic (L), and temporal and logical software monitor of the program flow and detec-
tion of static faults and short circuits (for multiple I/O).
Whenever DC = Medium is used in the circuit examples for safety digital inputs, any of the measures
for input devices with DC ³ 90 % can be used from ISO 13849-1 [10].
30.03.2017
Values
"On", "Off"
"Not used", "1 channel", "2 channel equivalent", "2
channel antivalent"
"Disabled", "Enabled"
"1 ms", "2 ms", "5 ms", "10 ms", "15 ms", "30 ms",
"50 ms", "100 ms", "200 ms", "500 ms"
"10 ms", "20 ms", "30 ms", "40 ms", "50 ms",
"60 ms", "70 ms", "80 ms", "90 ms", "100 ms",
"150 ms", "200 ms", "250 ms", "300 ms", "400 ms",
"500 ms", "750 ms", "1 s", "2 s", "3 s", "4 s", "5 s",
"10 s", "20 s", "30 s"
AC500-S
AC500-S Safety Modules
DI581-S digital safety input module > Circuit examples
rd
party PROFINET F-Host systems.
Default
"On"
"Not used"
"Disabled"
"5 ms"
"50 ms"
85