NOTICE!
SIL (IEC 61508 ed. 2 and IEC 62061) and PL (ISO 13849) reachable in your safety application
depend on the wiring of your sensors and actors to DX581-S module
ples" on page 117.
DX581-S contains 8 safety digital inputs 24 V DC separated in two groups (2.0 ... 2.3 and 4.0 ... 4.3) and 8
safety digital transistor outputs with no potential separation between the channels.
The inputs/outputs are not electrically isolated from the other electronic circuitry of the module.
30.03.2017
DX581-S digital safety input/output module > Purpose
AC500-S
AC500-S Safety Modules
Ä Chapter 3.4.7 "Circuit exam-
107