Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function Block-Specific Error and Status Codes
Table 43: FB-specific error codes
DiagCode
State Name
C001
Error
Short-circuit
C002
Error
Open-circuit
C003
Reset Error 1
C004
Reset Error 2
286
State Description and Output Setting
The FB detected that two or more S_ModeX are TRUE, e.g., short-circuit
of cables.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
The FB detected that all S_ModeX are FALSE: The period following a
falling S_ModeX trigger exceeds ModeMonitorTime, e.g., open-circuit of
cables.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
Static Reset signal detected in state C001.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE
Static Reset signal detected in state C002.
Ready = TRUE
Error = TRUE
S_AnyModeSel = FALSE
All S_ModeXSel = FALSE