Mounting, Dimensions And Electrical Connection - ABB AC500-S Safety User Manual

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Fig. 18: 2 channel antivalent mode implemented in DI581-S
NOTICE!
2 channel equivalent and 2 channel antivalent modes are implemented in DI581-S and DX581-S
module to handle relatively static safety signals, e.g., those for emergency stop devices.
If frequently changing signals, like those from light curtains, laser scanners, door switches, etc. must
be handled by DI581-S and DX581-S, then it is highly recommended to configure related channels in
1 channel mode and do 2 channel equivalent and 2 channel antivalent evaluation at SM560-S Safety
CPU using PLCopen Safety FBs SF_Equivalent and SF_Antivalent (
lent" on page 269 and

3.3.3 Mounting, dimensions and electrical connection

The input modules can be plugged only on spring-type TU582-S I/O Terminal Unit. The unique mechanical
coding on I/O Terminal Units prevents a potential mistake of placing the Non-safety I/O module on Safety I/O
Terminal Unit and the other way around.
30.03.2017
DI581-S digital safety input module > Mounting, dimensions and electrical connection
Ä Chapter 4.6.6.3 "SF_Antivalent" on page 274).
Ä Chapter 4.6.6.2 "SF_Equiva-
AC500-S
AC500-S Safety Modules
79

Hide quick links:

Advertisement

Table of Contents
loading