Error
Compo-
Device Module
class
nent or
Inter-
face
E2
1 or 9
1 ... 4
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
30.03.2017
Channel
1
0
30
1
30
1
30
1
30
1
30
1
30
1
30
1
30
1
30
2
30
2
30
2
AC500-S
AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
Error
Error text
43
Internal error
48
Overvoltage or
undervoltage
detected
43
Internal error
40
Wrong firm-
ware version
28
Boot project
download error
1
Wrong user
data
0
Operation fin-
ished.
18
Internal error
12
Flash read
error
18
Internal error
52
Internal error
43
Internal error
Remedy
For Safety PLC: Check
Safety PLC switch address
setting. Restart Safety PLC.
If this error persists, replace
Safety PLC
Restart Safety PLC. Check
Safety PLC setting for
power supply error. If this
error persists, replace
Safety PLC.
Contact ABB technical sup-
port. Replace Safety PLC.
Update Safety PLC firm-
ware. Restart Safety PLC. If
this error persists, replace
Safety PLC.
Reload boot project. If this
error persists, replace
Safety PLC.
Delete user data from
Safety PLC. Restart Safety
PLC and write user data
again.
Change Safety PLC switch
address setting or remove
SD-Card from non-safety
PLC.
Restart Safety PLC. If this
error persists, replace
Safety PLC.
Contact ABB technical sup-
port. Replace Safety PLC.
Restart Safety PLC. If this
error persists, replace
Safety PLC. Contact ABB
technical support.
Contact ABB technical sup-
port. Replace Safety PLC.
Contact ABB technical sup-
port. Replace Safety PLC.
Contact ABB technical sup-
port. Replace Safety PLC.
43