Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
96 ➔ 30 ms
112 ➔ 50 ms
128 ➔ 100 ms
144 ➔ 200 ms
160 ➔ 500 ms
Compare calculated Dec_InputChannel0 (
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
3.
Repeat step 2 for the rest of digital input channels (Input 1, Input 2, ... Input 7).
4.
Compare that "2 channel configuration 0/4" parameter in "DX581-S" tab have the same value as
"Inputs 0/4, discrepancy time" parameter in "DX581-S Configuration" tab.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
Fig. 132: Compare "DX581-S" tab and "DX581-S Configuration" tab
1
2 channel configuration 0/4" parameter in
"DX581-S" tab
5.
Repeat Step 4 for the rest of input channel combinations:
Inputs 1/5, discrepancy time
n
n
Inputs 2/6, discrepancy time
n
Inputs 3/7, discrepancy time
6.
Refer to "DX581-S" tab and calculate "Output channel 0" decimal equivalent (Dec_OutputChannel0)
as:
Dec_OutputChannel0 = Detection_Value + Output_Value + 1
where
Detection_Value:
0 ➔ Off
30.03.2017
Checklists for AC500-S Commissioning
Ä step 2) with "Input 0, channel configuration value".
2
"Inputs 0/4, discrepancy time" parameter in
"DX581-S Configuration" tab
AC500-S
Safety I/Os
423