Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
State Name
8002
ESPE Inter-
rupted 1
8003
Wait for Reset
1
8004
External Func-
tion Test
330
State Description and Output Setting
The FB has detected a safety demand.
The switch has not been automatically tested yet.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
Wait for rising trigger of Reset after state 8002.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
The automatic sensor test was faulty.
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has been acti-
vated at the FB (NoExternalTest = FALSE).
A negative signal edge at the sensor is required.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE