Technical Data - ABB AC500-S Safety User Manual

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

LED
Description
Outputs
Digital output
0 ... 7
Channel error
UP
Process voltage
+24 V DC via
terminal
PWR
+3.3 V voltage
from IO-Bus
ERR1
Module error
indicator 1
ERR2
Module error
indicator 2

3.4.9 Technical data

NOTICE!
DX581-S-XC version is available for usage in extreme environmental conditions (
"System data for AC500-S-XC" on page 446).
30.03.2017
Colour
LED = OFF
Yellow
Output = OFF
Red
No channel error
Green
Process supply
voltage is missing
Green
+3.3 V IO-Bus
voltage is not avail-
able
Red
No module error
Red
AC500-S
AC500-S Safety Modules
DX581-S digital safety input/output module > Technical data
LED = ON
Output = ON
Channel error
Process supply
voltage OK
+3.3 V IO-Bus
voltage is available
Module error which
leads to a SAFE
STOP state
LED flashes
--
--
--
--
Module passivation
and/or acknowl-
edgement request
(alternating blinking)
Ä Appendix
127

Hide quick links:

Advertisement

Table of Contents
loading