4.6.3 SafetyBase_PROFIsafe_AC500_V22_Ext.lib

This library includes a PROFIsafe Stack implementation (PROFISAFESTACK POU), which is a key F-Host
component.
NOTICE!
Old versions
SafetyBase_PROFIsafe_AC500_V22.lib, Version 1.0.0, library CRC: 7f64e267, license activation
with PS501-S License Enabling Package
SafetyBase_PROFIsafe_AC500_V22.lib, Version 1.0.0, library CRC: c688eb23, special OEM ver-
sion of PROFIsafe library
are NOT for use in new AC500-S customer projects.
NOTICE!
Loop-back check via Bit 7 in Status / Control Byte of PROFIsafe telegram is implemented, which
means that no further considerations against systematic loop-back configuration errors shall be per-
formed by end-users (
DANGER!
Not more than one communication error (CE_CRC or Host_CE_CRC output signals become equal to
TRUE) per 100 hours is allowed to be acknowledged by the operator using OA_C input signal without
consulting the responsible safety personnel (
This function block represents PROFIsafe F-Device instance in the PROFIsafe F-Host to control and monitor
the status of the given F-Device [3].
30.03.2017
Ä www.profisafe.net for further details).