Checklists for AC500-S Commissioning

Checklist for operation, maintenance and repair

Nr.
Item to check
7.
Verify that:
n
Address setting is correct
n
Assignment of signal inputs is complete
n
Assignment of signal outputs is complete
Assignment of unused inputs is complete
n
n
All terminal blocks are plugged
8.
Verify that correct firmware versions are used for
dependent non-safety components, like CM579-PNIO
(V2.6.5.1 or higher), CI50x (V3.2.0 or higher) and
PM5xx CPUs (V2.2.1 or higher).
Contact ABB technical support if needed.
Reviewer(s):
Machine/Application <ID>:
Signature:
Date:
6.4 Checklist for operation, maintenance and repair
Nr.
Item to check
1.
Make sure that all Safety modules are properly
placed on their positions at the terminal base (Safety
CPU) or terminal units (Safety I/Os) and stable con-
tact between terminals and safety modules is
assured.
2
Check that proper temperature monitoring measures
(e.g., temperature sensors could be placed in the
control cabinet and connected to AI581-S safety
analog input channels) are implemented in the control
cabinet where AC500-S safety modules are placed, if
the operating temperature range for AC500-S Safety
PLC cannot be guaranteed.
Note:
Safety digital outputs of DX581-S module have
internal built-in overtemperature protection and
always deliver fail-safe "0" values in case of overtem-
perature.
410
Fulfilled (Yes / No)?
Fulfilled (Yes / No)?
AC500-S
Comment
Comment
30.03.2017