reflect
- Output of browser commands (for test purposes)
pid
- It shows the project ID
pinf
- It shows project information in AC500 format
getprgprop
- It shows program properties in AC500 format
getprgstat
- It shows program status in AC500 format
setpwd
- It sets PLC password (it is needed during logging-on). This command is active only if
delpwd
- It deletes PLC password. This command is active only if SM560-S "Enable debug"
rtsinfo
- It shows firmware and boot project information in AC500 format
proddata
- It shows SM560-S production data in AC500 format
diagreset
- It resets diagnosis system of SM560-S Safety CPU
diagack all
- It acknowledges all errors
diagack x
- It acknowledges all errors of class x (x= 1 .. 4)
diagshow all - It shows all errors in AC500 format
diagshow x
- It shows all errors of class x
delappl
- It deletes boot project in the Flash memory. This command is executed only in
deluserdat:
- It deletes user data in the Flash memory. This command is executed only in DEBUG
applinfo
- It shows the application information, e.g., results of time profiling using functions
applinfo reset - It resets all application information, e.g., time measurement values.
None of the above-mentioned SM560-S PLC browser commands changes the state (e.g., from RUN to
DEBUG RUN or DEBUG STOP, etc.) of SM560-S Safety CPU.
NOTICE!
The following PLC Browser commands from Safety CPU can influence SM560-S state:
resetprg:
It prepares SM560-S restart with initial variable values. SM560-S changes its state, e.g., from
RUN to DEBUG STOP. This command is active only if SM560-S "Enable debug" parameter was
set to "ON" .
resetprgorg:
It restores SM560-S original state (all variables, Flash memory sections, etc. get original values).
SM560-S changes its state, e.g., from RUN to DEBUG STOP. This command is active only if
SM560-S "Enable debug" parameter was set to "ON" .
30.03.2017
System configuration and programming > Programming of AC500-S Safety CPU
SM560-S "Enable debug" parameter was set to "ON".
parameter was set to "ON".
DEBUG STOP state of SM560-S Safety CPU. After SM560-S restart, one shall check
that no boot project is available in SM560-S Safety CPU. This command is active only
if SM560-S "Enable debug" parameter was set to "ON".
STOP state of SM560-S Safety CPU. It is executed immediately and is active only if
SM560-S "Enable debug" parameter was set to "ON".
SF_APPL_MEASURE_BEGIN and SF_APPL_MEASURE_END.