DANGER!
The safety values for safety outputs of DX581-S (-XC) module are only valid if the parameter Detec-
tion = "On" (internal test of output transistors is active). If the parameter Detection = "Off" then contact
ABB technical support to obtain proper safety values.
DANGER!
The average temperature (MTBF calculation base) for both the extended temperature range (–40 °C
... +70 °C) as well as for standard temperature range (0 °C ... +60 °C) is defined to 40 °C.
Ensure that average operating temperature for used AC500-S modules does not exceed 40 °C.
The detailed safety values for AC500-S Safety modules can be obtained on request.

2.5 Qualified personnel

AC500-S Safety PLC may only be set up and used in conjunction with this documentation.
Safety application engineer of AC500-S Safety PLC
Commissioning and operation of AC500-S Safety PLC may only be performed by the qualified personnel
who is authorized to commission safety devices, systems and circuits in accordance with established func-
tional safety practices and standards.
The following basic knowledge of AC500 system is required to correctly understand this AC500-S Safety
User Manual:
n
AC500 automation system
n
PS501 Control Builder Plus / ABB Automation Builder Programming Environment (system configuration
and programming in ST, LAD and FBD programming languages).

2.6 Lifecycle

All AC500-S safety modules have a maximum life of 20 years. This means that all AC500-S safety modules
shall be taken out of service or replaced by new AC500-S safety modules at least one week before the
expiry of 20 years (counted from the date of delivery by ABB).

2.7 Installation of safety modules

The following rules shall be taken into account for installing Safety Modules:
n
The installation must be done according to the documentation with appropriate facilities and tools.
n
The installation of the devices may be done only in de-energized condition and carried out by the quali-
fied personnel.
n
The general safety regulations and applicable national safety regulations shall be strictly observed.
n
The electrical installation shall be carried out in accordance with relevant regulations.
n
Take the necessary protective measures against static discharge.