Typical Timing Diagram
Activate
MutingEnable
S_AOPD_In
MutingSwitch11
MutingSwitch12
MutingSwitch21
MutingSwitch22
S_AOPD_Out
S_MutingAcitve
Error
DiagCode
Fig. 115: Timing diagram for SF_MutingPar
The FB detects the following error conditions:
n
DiscTime11_12 and DiscTime21_22 have been set to values less than T#0s or greater than T#4s.
n
MaxMutingTime has been set to a value less than T#0s or greater than T#10min.
The discrepancy time for the MutingSwitch11/MutingSwitch12 or MutingSwitch21/MutingSwitch22 sensor
n
pairs has been exceeded.
n
The muting function (S_MutingActive = TRUE) exceeds the maximum muting time MaxMutingTime.
n
Muting sensors MutingSwitch11, MutingSwitch12, MutingSwitch21, and MutingSwitch22 are activated in
the wrong order.
n
Muting sequence starts without being enabled by MutingEnable
n
A faulty muting lamp is indicated by S_MutingLamp = FALSE.
n
A static Reset condition is detected in state 8001 and 8003.
Error Behavior
In the event of an error, the S_AOPD_Out and S_MutingActive outputs are set to FALSE. The DiagCode
output indicates the relevant error code and the Error output is set to TRUE.
A restart is inhibited until the error conditions are cleared and the Safe state is acknowledged with Reset by
the operator.