Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
64 ➔ On
Output_Value:
0 ➔ Not used
128 ➔ Used
Compare calculated Dec_OutputChannel0 (
have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
7.
Repeat step 6 for the rest of digital output channels (Channel 1, Channel 2, ... Channel 7).
424
Ä step 7) with "Output 0, channel configuration". They