DiagCode
State Name
8005
ESPE Inter-
rupted
External Test
8006
End External
Test
8010
ESPE Free No
Test
30.03.2017
State Description and Output Setting
The automatic sensor test was faulty.
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has been acti-
vated at the FB (NoExternalTest = FALSE).
A TRUE signal at the sensor is required.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
The automatic sensor test was faulty.
An external manual sensor test is necessary.
The support for the necessary external manual sensor test has been acti-
vated at the FB (NoExternalTest = FALSE).
The external manual test is complete.
The FB detected a complete sensor switching cycle (external controlled).
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = FALSE
The FB has not detected a safety demand.
The sensor has not been tested automatically.
Ready = TRUE
S_OSSD_Out = TRUE
S_TestOut = TRUE
TestPossible = TRUE
TestExecuted = FALSE
Error = FALSE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib