ABB AC500-S Safety User Manual page 325

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Name
Data Type
S_OSSD_Out
BOOL
S_TestOut
BOOL
TestPossible
BOOL
TestExecuted
BOOL
Error
BOOL
DiagCode
WORD
Notes: OSSD: Output Signal Switching Device.
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
FALSE
Safety related output indicating the status of the
ESPE.
FALSE: The sensor has a safety-related action
request or test error. TRUE: The sensor has no
safety-related action request and no test error.
TRUE
Coupled with the test input of the sensor.
FALSE: Test request issued.
TRUE: No test request.
FALSE
Feedback signal to the process.
FALSE: An automatic sensor test is not possible.
TRUE: An automatic sensor test is possible.
FALSE
A positive signal edge indicates the successful
execution of the automatic sensor test.
FALSE:
- An automatic sensor test was not executed yet.
- An automatic sensor test is active.
- An automatic sensor test was faulty.
TRUE: A sensor test was executed successfully.
Ä Table 32 "General Output Parameters"
FALSE
on page 267
Ä Table 32 "General Output Parameters"
16#0000
on page 267
AC500-S
Configuration and programming
325

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents