AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
The next figure shows LED states of SM560-S Safety CPU, which can be observed during its start-up.
SM560-S
PWR
DIAG
RUN
I-ERR
E-ERR
1
Fig. 10: LED states of SM560-S Safety CPU during start-up
1
State 1 – Hardware reset
2
State 2 – Initialisation
3
State 3 – LED test
4
State 4 – End of start-up
SM560-S error messages are aggregated together with other communication module error messages in
SM560-S and PM5xx CPUs. Following Table includes a list of error messages related to SM560-S Safety
CPU (all of them can be observed on PM5xx using, e.g., "diagshow all" PLC browser command).
Table 4: List of error messages for SM560-S
Error
Compo-
Device Module
class
nent or
Inter-
face
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 ... 4
255
E2
1 or 9
1 ... 4
42
SM560-S
PWR
DIAG
RUN
I-ERR
E-ERR
2
Channel
30
1
30
2
30
3
1
0
AC500-S
SM560-S
PWR
DIAG
RUN
I-ERR
E-ERR
3
Error
Error text
2
Internal PRO-
FIsafe initiali-
zation error
2
Internal PRO-
FIsafe error
30
PROFIsafe
configuration
error
17
Access test
failed
SM560-S
PWR
DIAG
RUN
I-ERR
E-ERR
4
Remedy
Restart Safety PLC. If this
error persists, replace
Safety PLC. Contact ABB
technical support.
Restart Safety PLC. If this
error persists, replace
Safety PLC. Contact ABB
technical support.
Check F-Parameter config-
uration of I/O module and
reload boot project.
For Safety PLC: Check
Safety PLC switch address
setting. Restart Safety PLC.
If this error persists, replace
Safety PLC.