Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function Block-Specific Error and Status Codes
Table 70: FB-specific error codes
DiagCode
State Name
C001
Reset Error 1
C002
Reset Error 2
C003
Error Muting
Lamp
352
State Description and Output Setting
Static Reset condition detected after FB activation in state 8001.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Static Reset condition detected in state 8003.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE
Error detected in muting lamp.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = TRUE