ABB AC500-S Safety User Manual page 327

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

If S_AutoReset = FALSE, a rising trigger is required at Reset.
After transition of S_OSSD_In to TRUE, the optional startup inhibit can be reset by a rising edge at the Reset
input.
After block activation, the optional startup inhibit can be reset by a rising edge at the Reset input.
Function Block-Specific Error and Status Codes
Table 64: FB-specific error codes
DiagCode
State Name
C000
Parameter
Error
C001
Reset Error 1
C002
Reset Error 2
C003
Reset Error 3
30.03.2017
State Description and Output Setting
Invalid value at the TestTime parameter.
Values between 0 ms and 150 ms are possible.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Static Reset condition detected after FB activation.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Static Reset condition detected in state 8003.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
Static Reset condition detected in state C010.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = FALSE
Error = TRUE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
327