ABB AC500-S Safety User Manual page 64

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

AC500-S Safety Modules
Generic Safety I/O module behaviour > Safety I/O module states
RUN (module passivation with a command): Alternating blinking of ERR1 & ERR2 LEDs
PROFIsafe communication is up and running. The safety application is running without any detected errors.
The module and all its channels are passivated because the safety application on the Safety CPU requested
a module passivation (activate_FV_C = 1 was set).
The fail-safe value "0" is transferred to the Safety CPU for all passivated input channels. All passivated
output channels have a state of "0". The PROFIsafe diagnostic bit(s) for all channels have the state of "0" to
indicate that fail-safe values are transferred.
PROFIsafe status bits in the F-Host for Safety I/O module:
FV_activated_S = 1
Process data bits in the Safety I/O module process image:
PROFIsafe diagnostic bit = 0
Channel process value = 0
Reintegration request bit = 0
64
1.0 I0-
PWR
2.0I0+
3.0 I2-
1.1 FE
2.1
3.1 FE
1.2 I1-
2.2I1+
3.2 I3-
1.3 FE
2.3
3.3 FE
1.4
2.4
3.4
ADDR
2.5
1.5
3.5
x10H
4
3
5
6
2
2.6
3.6
1.6
1
7
0
8
F
9
E
A
1.7
2.7
3.7
D
B
C
ADDR
1.8 UP
2.8UP
3.8 UP
x01H
4
5
3
2
6
1.9 ZP
2.9ZP
3.9 ZP
1
7
0
8
F
9
A
E
D
B
C
ERR1
UP 24VDC 2W
AC500-S
AI581-S
4.0I2+
4.1
4.2I3+
4.3
4.4
4.5
4.6
4.7
4.8UP
4.9ZP
ERR2
4SAI
Safety Analog Input
30.03.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents