Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Function Block-Specific Error and Status Codes
Table 82: FB-specific error codes
DiagCode
State Name
C001
Reset Error 1
C002
Reset Error 2
C010
Control Error
C111
Init Error
C211
Lock Error
Table 83: FB-specific status codes (no error):
DiagCode
State Name
0000
Idle
8001
Init
384
State Description and Output Setting
Static Reset signal in state 8001.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Static Reset signal in state 8003.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Static signal at ProcessControl in state 8010.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Simultaneous rising trigger at Reset and ProcessControl in state 8001.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
Simultaneous rising trigger at Reset and ProcessControl in state 8003.
Ready = TRUE
S_OutControl = FALSE
Error = TRUE
State Description and Output Setting
The function block is not active (initial state).
Ready = FALSE
S_OutControl = FALSE
Error = FALSE
Block activation startup inhibit is active. Reset required.
Ready = TRUE
S_OutControl = FALSE
Error = FALSE