Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
128 ➔ 100 ms
144 ➔ 200 ms
160 ➔ 500 ms
Compare calculated Dec_InputChannel0 (
They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
3.
Repeat step 2 for the rest of digital input channels (Input 1, Input 2, ... Input 15).
4.
Compare that "2 channel configuration 0/8" parameter in "DI581-S" tab have the same value as "Inputs
0/8, discrepancy time" parameter in "DI581-S Configuration" tab.
The values have to be the same.
If they are not the same, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
Fig. 130: Compare "DI581-S" tab and "DI581-S Configuration" tab
1
"2 channel configuration 0/8" parameter in
"DI581-S" tab
5.
Repeat step 4 for the rest of channel combinations:
n
Inputs 1/9, discrepancy time
n
Inputs 2/10, discrepancy time
n
Inputs 3/11, discrepancy time
n
Inputs 4/12, discrepancy time
n
Inputs 5/13, discrepancy time
n
Inputs 6/14, discrepancy time
Inputs 7/15, discrepancy time
n
30.03.2017
Checklists for AC500-S Commissioning
Ä step 2) with "Input 0, channel configuration value".
2
"Inputs 0/8, discrepancy time" parameter in
"DI581-S Configuration" tab
AC500-S
Safety I/Os
421