The safety function will be provided by the actuator itself. Therefore the FB only initiates the request, moni-
tors it, and sets the output when the actuator acknowledges the Safe state. This will be indicated with the
"S_SafetyActive" output.
This FB does not define any generic actuator-specific parameters. They should have been specified in the
generic actuator itself. It switches the generic actuator from the operation mode to a safe state.
Table 78: FB Name: SF_SafetyRequest
Name
Data Type
VAR_INPUT
Activate
BOOL
S_OpMode
BOOL
S_Acknowledge
BOOL
Reset
BOOL
MonitoringTime
TIME
VAR_OUTPUT
Ready
BOOL
S_SafetyActive
BOOL
S_SafetyRequest
BOOL
Error
BOOL
DiagCode
WORD
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
Ä Table 31 "General Input Parameters"
FALSE
on page 266
FALSE
Variable.
Requested mode of a generic safe actuator.
FALSE: Safe mode is requested.
TRUE: Operation mode is requested.
FALSE
Variable.
Confirmation of the generic actuator, if actuator is
in the Safe state.
FALSE: Operation mode (non-safe).
TRUE: Safe mode.
Ä Table 31 "General Input Parameters"
FALSE
on page 266
T#0s
Constant.
Monitoring of the response time between the
safety function request (S_OpMode set to FALSE)
and the actuator acknowledgment (S_Acknowl-
edge switches to TRUE).
FALSE
Ä Table 32 "General Output Parameters"
on page 267
FALSE
Confirmation of the Safe state.
FALSE: Non-safe state.
TRUE: Safe state.
FALSE
Request to place the actuator in a safe state.
FALSE: Safe state is requested.
TRUE: Non-safe state.
Ä Table 32 "General Output Parameters"
FALSE
on page 267
Ä Table 32 "General Output Parameters"
16#0000
on page 267
AC500-S
Configuration and programming
375