ABB AC500-S Safety User Manual page 309

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Function Block-Specific Error and Status Codes
Table 55: FB-specific error codes
DiagCode
State Name
C001
Error B1
C002
Error B2
C003
Error B1&B2
Table 56: FB-specific status codes (no error):
DiagCode
State Name
0000
Idle
8000
Buttons Actu-
ated
8001
Init
8004
Buttons
Released
30.03.2017
State Description and Output Setting
S_Button1 was TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
S_Button2 was TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
The signals at S_Button1 and S_Button2 were TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
State Description and Output Setting
The function block is not active (initial state).
Ready = FALSE
Error = FALSE
S_TwoHandOut = FALSE
Both buttons actuated correctly. The safety related output is enabled.
Ready = TRUE
Error = FALSE
S_TwoHandOut = TRUE
Function block is active, but in the Init state.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
No button is actuated.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents