Advertisement

Name
Data Type
Ready
BOOL
S_AOPD_Out
BOOL
S_MutingActive
BOOL
Error
BOOL
DiagCode
WORD
Notes: Line control of muting sensor signals must be active in the safety loop
Example for SF_MutingPar_2Sensor with two reflecting light barriers
1
If reflection light barriers are used as muting sensors, they are generally arranged diagonally. In general, this
arrangement of reflection light barriers as muting sensors requires only two light barriers, and only
S_MutingSwitch11 (MS_11) and S_MutingSwitch12 (MS_12) are allocated.
Muting conditions
Muting condition 1 (to 8011) (MS_11 is the first entry switch actuated). Start timer DiscTimeEntry and Max-
MutingTime:
MutingEnable AND R_TRIG at MS_11 AND NOT MS_12
Muting condition 2 (to 8311) (MS_12 is the first entry switch actuated). Start timer DiscTimeEntry and Max-
MutingTime:
MutingEnable AND NOT MS_11 AND R_TRIG at MS_12
Muting condition 3 (from 8011 to 8012) (MS_12 is the second entry switch actuated):
Stop timer DiscTimeEntry:
MutingEnable AND MS_11 AND R_TRIG at MS_12
30.03.2017
Initial Value
FALSE
FALSE
FALSE
FALSE
16#0000
Transmitter
MS_11
MS_12
Receiver
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Description, Parameter Values
Ä Table 32 "General Output Parameters"
on page 267
Safety related output, indicates status of the
muted guard.
FALSE: AOPD protection field interrupted and
muting not active.
TRUE: AOPD protection field not interrupted or
muting active.
Indicates status of Muting process.
FALSE: Muting not active.
TRUE: Muting active.
Ä Table 32 "General Output Parameters"
on page 267
Ä Table 32 "General Output Parameters"
on page 267
Danger
zone
361