Fig. 125: Timing diagrams for SF_EDM: S_StartReset = TRUE
The following conditions force a transition to the Error state:
n
Invalid static Reset signal in the process.
n
Invalid EDM signal in the process.
n
S_OutControl and Reset are incorrectly interconnected due to programming error.
Error Behavior
In error states, the outputs are as follows:
n
In the event of an error, the S_EDM_Out is set to FALSE and remains in this safe state.
n
An EDM error message must always be reset by a rising trigger at Reset.
n
A Reset error message can be reset by setting Reset to FALSE.