ABB AC500-S Safety User Manual page 279

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

DiagCode
State Name
8014
Wait for NC
8005
From Active
Wait
4.6.6.4
SF_ModeSelector
Standards
Requirements
MRL 98/37/EC,
1.2.3. Starting
Annex I
... It must be possible to start machinery only by voluntary actuation of a control pro-
vided for the purpose ...The same requirement applies: ...
- when effecting a significant change in the operating conditions ...
1.2.5 ... mode selector which can be locked in each position. Each position of the
selector must correspond to a single operating or control mode ...
EN ISO 12100-2:
4.11.10 Selection of Control and Operating Modes
2003
... shall be fitted with a mode selector which can be locked in each position. Each posi-
tion of the selector shall be clearly identifiable and shall exclusively enable one control
or operating mode to be selected...
IEC 60204-1, Ed.
9.2.3 Operating Modes
5.0 : 2003
... When a hazardous condition can result from a mode selection, unauthorized and/or
inadvertent selection shall be prevented by suitable means (e.g. key operated switch,
access code). Mode selection by itself shall not initiate machine operation. A separate
action by the operator shall be required. ... Indication of the selected operating mode
shall be provided ...
EN 954-1: 1996
5.4 Manual reset
ISO 12100-2:
4.11.4: Restart following power failure/spontaneous restart
2003
30.03.2017
State Description and Output Setting
ChannelNO has been switched to FALSE - waiting for ChannelNC to be
switched to TRUE; discrepancy timer started.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE
One channel has been switched to inactive; waiting for the second channel
to be switched to inactive too.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE
AC500-S
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
279

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents