3.4.9.3
Technical data of non-safety test pulse outputs
Data
Number of test pulse channels per module (transistor test pulse
outputs)
Terminals of the channels T0, T1
Terminals of the channels T2 to T3
Terminals of reference potential for all test pulse outputs (minus
pole of the process supply voltage, signal name ZP)
Terminals of common power supply voltage for all outputs (plus
pole of the process supply voltage, signal name UP)
Output voltage for signal 1
Length of test pulse 0 phase
Output current
Data
Rated value, per channel
Maximum value (all channels together)
Short-circuit proof / overload proof
Output current limitation
Resistance to feedback against 24V signals
Cable length
Data
Max. cable length, shielded
Max. cable length, unshielded
3.4.10

Ordering data

Type
DX581-S
DX581-S-XC
30.03.2017
Description
DX581-S:S500, Safety Digital I/O
Module 8SDI/SDO
DX581-S-XC:S500, Safety Digital I/O
Module 8SDI/SDO, Extreme Condi-
tions
DX581-S digital safety input/output module > Ordering data
Order code
1SAP 284 100 R0001
1SAP 484 100 R0001
AC500-S
AC500-S Safety Modules
Value Unit
4
1.0, 1.2
3.0, 3.2
1.9 ... 4.9
1.8 ... 4.8
UP – 0.8 V
1 ms
Value Unit
10 mA
40 mA
yes
65 mA
yes
Value Unit
1000 m
600 m
135