ABB AC500-S Safety User Manual page 312

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Table 57: FB Name: SF_TwoHandControlTypeIII
Name
Data Type
VAR_INPUT
Activate
BOOL
S_Button1
BOOL
S_Button2
BOOL
VAR_OUTPUT
Ready
BOOL
S_TwoHandOut
BOOL
Error
BOOL
DiagCode
WORD
Notes: No Reset input or Error output is required, because no test can be performed on both switches.
312
Initial Value
Description, Parameter Values
FALSE
Ä Table 31 "General Input Parameters"
on page 266
FALSE
Variable.
Input of button 1 (for category 3 or 4: two antiva-
lent contacts)
FALSE: Button 1 released.
TRUE: Button 1 actuated.
FALSE
Variable.
Input of button 2 (for category 3 or 4: two antiva-
lent contacts)
FALSE: Button 2 released.
TRUE: Button 2 actuated.
FALSE
Ä Table 32 "General Output Parameters"
on page 267
FALSE
Safety related output signal.
FALSE: No correct two hand operation.
TRUE: S_Button1 and S_Button2 inputs changed
from FALSE to TRUE within 500 ms and no error
occurred. The two hand operation has been per-
formed correctly.
Ä Table 32 "General Output Parameters"
FALSE
on page 267
Ä Table 32 "General Output Parameters"
16#0000
on page 267