Table 81: FB Name: SF_OutControl
Name
Data Type
VAR_INPUT
Activate
BOOL
S_SafeControl
BOOL
ProcessControl
BOOL
StaticControl
BOOL
S_StartReset
BOOL
S_AutoReset
BOOL
Reset
BOOL
VAR_OUTPUT
Ready
BOOL
S_OutControl
BOOL
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
FALSE
Ä Table 31 "General Input Parameters"
on page 266
FALSE
Variable.
Control signal of the preceding safety FB.
Typical function block signals from the library
(e.g., SF_EStop, SF_GuardMonitoring, SF_Two-
HandControlTypeII, and/or others).
FALSE: The preceding safety FB's are in safe
state.
TRUE: The preceding safety FB's enable safety
control.
FALSE
Variable or constant.
Control signal from the functional application.
FALSE: Request to set S_OutControl to FALSE.
TRUE: Request to set S_OutControl to TRUE.
FALSE
Constant.
Optional conditions for process control.
FALSE: Dynamic change at ProcessControl
(FALSE => TRUE) required after block activation
or triggered safety function. Additional function
start required.
TRUE: No dynamic change at ProcessControl
(FALSE => TRUE) required after block activation
or triggered safety function.
Ä Table 31 "General Input Parameters"
FALSE
on page 266
Ä Table 31 "General Input Parameters"
FALSE
on page 266
Ä Table 31 "General Input Parameters"
FALSE
on page 266
FALSE
Ä Table 32 "General Output Parameters"
on page 267
FALSE
Controls connected actuators.
FALSE: Disable connected actuators.
TRUE: Enable connected actuators.
AC500-S
Configuration and programming
381