ABB AC500-S Safety User Manual page 419

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
5 ➔ 5 %
6 ➔ 6 %
7 ➔ 7 %
8 ➔ 8 %
9 ➔ 9 %
10 ➔ 10 %
11 ➔ 11 %
12 ➔ 12 %
Min_Max_Value:
0 ➔ Min
128 ➔ Max
Compare calculated Dec_ExtConf0_2 (
tion". They have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
5.
Repeat step 4 for "Analog inputs 1/3 – Extended configuration" value.
30.03.2017
Checklists for AC500-S Commissioning
Ä Step 5) with "Analog inputs 0/2 – Extended configura-
AC500-S
Safety I/Os
419