Table 84: FB Name: SF_EDM
Name
Data Type
VAR_INPUT
Activate
BOOL
S_OutControl
BOOL
S_EDM1
BOOL
S_EDM2
BOOL
S_StartReset
BOOL
Reset
BOOL
MonitoringTime
TIME
VAR_OUTPUT
Ready
BOOL
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
FALSE
Ä Table 31 "General Input Parameters"
on page 266
FALSE
Variable.
Control signal of the preceeding safety FB's.
Typical function block signals from the library
(e.g., SF_OutControl, SF_TwoHandControlTypeII,
and/or others).
FALSE: Disable safety output (S_EDM_Out).
TRUE: Enable safety output (S_EDM_Out).
FALSE
Variable.
Feedback signal of the first connected actuator.
FALSE: Switching state of the first connected
actuator.
TRUE: Initial state of the first connected actuator.
FALSE
Variable.
Feedback signal of the second connected
actuator.
If using only one signal in the application, the user
must use a graphic connection to jumper the
S_EDM1 and S_EDM2 parameters. S_EDM1 and
S_EDM2 are then controlled by the same signal.
FALSE: Switching state of the second connected
actuator.
TRUE: Initial state of the second connected
actuator.
Ä Table 31 "General Input Parameters"
FALSE
on page 266
Ä Table 31 "General Input Parameters"
FALSE
on page 266
#0ms
Constant.
Max. response time of the connected and moni-
tored actuators.
FALSE
Ä Table 32 "General Output Parameters"
on page 267
AC500-S
Configuration and programming