Configuration and programming
AC500-S Libraries > DPRAM_SM5XX_SEND and DPRAM_SM5XX_REC in SysInt_AC500_V10.lib
DANGER!
It is of no concern to transfer data values from Safety CPU to Non-safety CPU (e.g., for diagnosis and
later visualization on the operator panels), but it is not recommended to transfer data values from Non-
safety CPU to Safety CPU. In the latter case, end-users have to define additional process-specific vali-
dation procedures in the safety program to check the correctness of the transferred non-safety data, if
they would like to use those non-safety values for safety functions.
260
AC500-S
30.03.2017