NOTICE!
When CoDeSys Safety is started for the first time in the ABB Automation Builder project, you
will be asked to manually confirm included safety library identification data (version number
and CRC). After this, safety library identification data are saved in the project.
If you change the safety library content and replace it on your hard disk, then the next time
you start CoDeSys Safety you will be informed that one of safety libraries changed. In the
properties window for safety libraries you will still observe an initially saved CRC
value. However, when you compile the project, you will get a CRC error message for the
changed library and the project will not be compiled, as a result.
To compile the project successfully, you will have to manually delete the selected safety
library, save the CoDeSys Safety project, open it again and add a new safety library with a
new CRC. In the latter case, the new safety library with a new CRC will be accepted and no
compilation error will be observed.
3.
If your configuration of F-Devices is final, you have to check that F-Parameter values from F-Parameter
tab are the same as those imported to CoDeSys Safety V2.3 (Go to "Resources" tab in CoDeSys
Safety 2.3 project and navigate to "Global Variables è PROFIsafe è F-Device instance").
DANGER!
You have to formally confirm that F-Parameter values from F-Parameter tab are the same as
those imported to CoDeSys Safety V2.3 (
tion program" on page 406 (Item 3)).
Fig. 86: F-Parameter values
30.03.2017
Configuration and programming
System configuration and programming > Programming of AC500-S Safety CPU