Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
DiagCode
State Name
8001
Init
8003
Wait for Reset
8011
Wait for Oper-
ator
8012
Guard Open
and Unlocked
8013
Guard Closed
but Unlocked
8014
Safety Return
322
State Description and Output Setting
Function block was activated and initiated.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = FALSE
Door is closed and locked, now waiting for operator reset
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = FALSE
Waiting for operator to either unlock request or reset.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = FALSE
Lock is released and guard is open.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = TRUE
Error = FALSE
Lock is released but guard is closed.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = TRUE
Error = FALSE
Return of S_SafetyActive signal, now waiting for operator acknowledge.
Ready = TRUE
S_GuardLocked = FALSE
S_UnlockGuard = FALSE
Error = FALSE
AC500-S
30.03.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents