Technical Data - ABB AC500-S Safety User Manual

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

"Warmstart on E2 failure" parameter setting of PM5xx Non-safety CPU has the following influence on the
SM560-S:
n
"Off" (Default)
In case of severe error (E2), no warm restart of PM5xx and of all its communication modules, including
SM560-S Safety CPU, will be done.
n
"On" (after E2 error and / or after short voltage dip)
In case of severe error (E2) and or short voltage dip, the warm restart of PM5xx and of all its communica-
tion modules, including SM560-S Safety CPU, will be done. After restart of SM560-S Safety CPU, Safety
I/O can be reintegrated using PROFIsafe F-Device reintegration scheme [3].

3.1.7 Technical data

Use SM560-S Safety CPU (up to SIL3 and PL e) with PM573, PM583, PM592 or others with the firmware
version from V2.2.1 (pay attention to the required TB units). SM560-S Safety CPU shall not to be used with
AC500-eCo CPUs.
NOTICE!
SM560-S-XC version is available for usage in extreme environmental conditions (
"System data for AC500-S-XC" on page 446).
30.03.2017
AC500-S
AC500-S Safety Modules
SM560-S Safety CPU > Technical data
Ä Appendix