ABB AC500-S Safety User Manual page 369

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

Table 75: FB Name: SF_EnableSwitch
Name
Data Type
VAR_INPUT
Activate
BOOL
S_SafetyActive
BOOL
S_Enable-
BOOL
SwitchCh1
S_Enable-
BOOL
SwitchCh2
S_AutoReset
BOOL
Reset
BOOL
VAR_OUTPUT
Ready
BOOL
S_Enable-
BOOL
SwitchOut
Error
BOOL
DiagCode
WORD
Typical Timing Diagrams
30.03.2017
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
Initial Value
Description, Parameter Values
FALSE
Ä Table 31 "General Input Parameters"
on page 266
FALSE
Variable or constant.
Confirmation of the safe mode (limitation of the
speed or the power of motion, limitation of the
range of motion).
FALSE: Safe mode is not active.
TRUE: Safe mode is active.
FALSE
Variable.
Signal of contacts E1 and E2 of the connected
enable switch.
FALSE: Connected switches are open.
TRUE: Connected switches are closed.
FALSE
Variable.
Signal of contacts E3 and E4 of the connected
enable switch.
FALSE: Connected switches are open.
TRUE: Connected switches are closed.
Ä Table 31 "General Input Parameters"
FALSE
on page 266
Ä Table 31 "General Input Parameters"
FALSE
on page 266
Ä Table 32 "General Output Parameters"
FALSE
on page 267
FALSE
Safety related output: Indicates suspension of
guard.
FALSE: Disable suspension of safeguarding.
TRUE: Enable suspension of safeguarding.
Ä Table 32 "General Output Parameters"
FALSE
on page 267
Ä Table 32 "General Output Parameters"
16#0000
on page 267
AC500-S
Configuration and programming
369