ABB AC500-S Safety User Manual page 41

Safety programmable logic controllers system
Hide thumbs Also See for AC500-S:
Table of Contents

Advertisement

LED
Description
DIAG
Diagnostics
RUN
Run mode indi-
cator
I-ERR
Internal device
error indicator
E-ERR
External error
indicator
DANGER!
The safety functionality and, as a result, safe process operation, is no more guaranteed by the
SM560-S Safety CPU in the DEBUG RUN (Non-safety) mode.
In case of DEBUG RUN (Non-safety) mode activation on SM560-S Safety CPU, the responsibility
for safe process operation lies entirely with the organisation and person responsible for the acti-
vation of DEBUG RUN (Non-safety) mode.
With the help of POU SF_SAFETY_MODE (
ther details) one can retrieve the information if SM560-S is in SAFETY or DEBUG (NON-SAFETY)
mode and, if required, stop or limit user application program execution.
30.03.2017
Colour
Status
Yellow
ON
BLINKING
OFF
Green
ON
BLINKING
OFF
Yellow
ON
BLINKING
OFF
Red
ON
BLINKING
OFF
Red
ON
BLINKING
OFF
Ä Chapter 4.6 "AC500-S Libraries" on page 224 for fur-
AC500-S
AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
Meaning
Configuration error
Not applicable
No configuration error
Safety CPU is in RUN (Safety) mode. The
application program is executed.
Not applicable
Safety CPU is in DEBUG STOP mode. The
application program is not executed.
Safety CPU is in DEBUG RUN (Non-safety)
mode. The application program is executed.
Firmware, boot project or boot code update
indication
Safety CPU is in DEBUG STOP mode. The
application program is not executed.
Internal device error leading to a SAFE STOP
state (no valid telegrams are generated by the
device)
Firmware or boot code update
No internal device error leading to a safe state
This LED can be set only from the user applica-
tion program using a special library POU
SF_E_ERR_LED_SET (
"AC500-S Libraries" on page 224 for further
details). One of possible use cases is the visu-
alization of important external device errors.
This LED can be set only from the user applica-
tion program using a special library POU
SF_E_ERR_LED_SET (
"AC500-S Libraries" on page 224 for further
details). One of possible use cases is the visu-
alization of light external device errors.
No external errors were identified.
Ä Chapter 4.6
Ä Chapter 4.6
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents